Metering, protection and automation

The wrong current transformer becomes noise, heat and rework in the panel

A poorly specified current transformer does not warn you before it fails. It shows up as electrical noise nobody can trace, as heat above what you expected inside the panel, or as a project that does not close because there is no room for the catalog model. The right question is not which model to buy. It is which specification your application demands.

  • São José dos Pinhais · PR · Brazil
  • Designed to ABNT NBR6856
  • Custom manufacturing in Brazil

What a current transformer solves in your circuit

A current transformer steps a high current, hard and dangerous to measure directly, down to a proportional secondary signal that metering, protection and automation instruments can read safely. The galvanic isolation between the power circuit and the control circuit is not a construction detail: it is the safety layer that protects the operator and the downstream instrumentation.

The principle is the electromagnetic induction described by Faraday's law: the current flowing in the primary creates a proportional field in the ferromagnetic core, and that field induces in the secondary a current set by the turns ratio. In a 100/5 A CT the ratio is 20, so the value read on the secondary must be multiplied by 20 to represent the actual circuit current.

The question that reaches our engineering team is almost never which CT to buy. It is which CT solves the real problem: noise that saturates the signal, heat above the design value, or a panel drawn without spare room for the transformer.

Window-type current transformer with a copper-wound toroidal core and two secondary output leads
Window-type CT: the circuit conductor passes through the toroidal core, which has no cut.

Metering CT or protection CT: the application decides everything

A metering CT must keep its accuracy within a narrow range under normal operating conditions. That is what makes the energy, power or current reading reflect what actually flows in the system. A protection CT needs something else: predictable behavior under fault conditions, including short-circuit currents far above rated, so the relay trips at the right time.

Treating the two as the same product is a common cause of rework. A CT sized only for metering can saturate at exactly the moment protection needs a reliable signal. The correct specification starts from the application, not from what is in stock.

The difference also shows in response time. A protection CT needs practically instantaneous action, because it feeds a relay that decides whether to open the circuit under fault. A metering CT works at the other extreme: it prioritizes an accurate, stable reading for monitoring and analysis of the electrical system in normal operation.

ABNT NBR6856 is the standard that governs current transformers in Brazil and classifies the CT in exactly these two categories, metering and protection. It is the reference used across the entire Toroid CT line, from accuracy class to overcurrent behavior.

Four Toroid current transformers side by side: one with output leads, one with a potted core, one with a plastic housing and one open toroidal unit
Metering and protection come from the same line. What changes from one CT to another is the specification, not the catalog.

Accuracy class: the number that decides whether your measurement can be trusted

Accuracy class expresses the maximum permissible error between the actual circuit current and the current indicated by the CT, within the specified operating range. In the Toroid line, accuracy starts at 0.3%, enough for revenue metering and for protection loops that cannot tolerate a reading error above what the design allows.

For whoever specifies, that number translates into field data you can trust without later adjustment: less calibration rework, fewer energy billing disputes, less risk of a protection decision made on a wrong reading.

Toroid current transformer with orange insulation and an identification label showing ratio 300/0,2 A, class 1,2C12,5, 50/60 Hz and lot number
Ratio, accuracy class, rated burden and lot are printed on the part.

Saturation and protection: how to avoid a wrong reading during a short circuit

Short-circuit current is the scenario in which a poorly sized CT fails without warning. The core saturates, the secondary signal stops being proportional to the actual current, and the protection relay may not trip at the right time, or may trip when it should not.

Saturation is the limit above which the instrument can no longer sustain its original electrical characteristics. Past that point, the secondary current no longer reproduces the primary current faithfully, the accuracy declared in the design no longer holds, and the CT has to be replaced. It is not a deviation that calibration can correct.

Electrical robustness under short circuit, covered in ABNT NBR5356-5, enters the sizing of a protection CT alongside the accuracy class and the overcurrent factor. In industrial automation and systems integration this weighs more than any isolated datasheet: a protection design is only as reliable as the weakest link in the measurement chain.

A correct specification is not bureaucracy. It is the difference between a project that works and one that generates rework.

Toroid do Brasil

Never leave the CT secondary open

Once the CT is installed, the secondary must never be left open. With no load connected to consume the energy induced by the magnetic flux in the core, the secondary voltage rises far above design, and three things become possible at the same time:

  • High voltage. The voltage induced with no load can cause internal arcing, overheating and insulation failure, compromising the transformer and creating repair or replacement cost.
  • Loss of measurement accuracy. With the secondary open, the proportional current can no longer be measured or monitored correctly, which propagates error to the protection and control systems that depend on that reading.
  • Personal safety risk. High voltage and structural failure of the transformer expose operators and maintenance staff to serious electric shock.

The practical rule is simple: the secondary of a current transformer is always connected to an appropriate rated burden. That is what preserves the equipment, the measurement accuracy and the safety of whoever works in the panel.

Construction types of current transformers

Before talking about range and accuracy, it helps to separate the constructions. The construction type defines how the CT is inserted into the circuit and, as a consequence, how much accuracy it can deliver and how much intervention the installation requires.

  • Window. Toroidal core crossed by the circuit conductor itself. Because the core has no cut, it is the construction with the lowest measurement error. In exchange, installation requires intervention in the system to pass the conductor through the window.
  • Split-core. Core divided into two parts that close around the conductor, which makes installation and maintenance much less invasive. The two cuts in the core cost accuracy compared with the window type.
  • Bar. The primary is a conductive bar, made of a high-conductivity, low-resistivity material to minimize losses, and the secondary produces the signal proportional to the current through it. Used for measuring high currents.
  • Bushing. Encapsulated in resin or in a robust insulator, used in high-voltage equipment such as circuit breakers and power transformers, where the insulating bushing itself has to withstand the system voltage level.
  • Wound. Primary and secondary windings connected in series with the circuit being measured. It requires opening the circuit for insertion, so it is the most invasive construction and is usually applied at lower currents.

The Toroid line is built around the window and split-core constructions, with or without resin encapsulation, within the voltage class of up to 1.5 kV. The others are listed here as a specification reference. If your project calls for another construction, describe the application so our team can evaluate it.

Current transformer with a black plastic housing, a central window for the conductor and secondary terminals on top
Window-type construction with housing, with the secondary terminals protected for panel mounting.

Compact CT for panels

Limited panel space should not compromise system performance. The Toroid compact CT was developed to fit an electrical panel whose space is already set by the design, without forcing the designer to redraw the panel to accommodate the transformer.

The inner diameter of 5 mm to 350 mm covers everything from individual conductors to busbars of larger cross section. This lets you keep the same line from the smallest to the largest panel in a project, which means fewer supplier changes and fewer item codes for purchasing to manage. When the standard does not cover the installation, we evaluate a custom design.

Split-core CT: when to install without de-energizing the circuit

In some projects, shutting down the circuit to install or replace a current transformer costs more than the part itself. In a plant that cannot stop, every hour of downtime has a price. The split-core CT opens around the energized conductor and removes the need to disconnect for installation or maintenance.

It is a construction feature that solves an operational problem, not only an electrical one: retrofit in an existing panel, scheduled maintenance without switching off the load, field replacement with no impact on production.

The counterpoint is in the construction types above: the two cuts in the core cost accuracy compared with the window type. When the application demands the lowest possible measurement error, that variable decides between the two constructions.

Two current transformers potted in black epoxy resin: on the left a window type with a continuous core, on the right a split-core unit with thumb screws that open the core
On the left, the window type with a continuous core. On the right, the split-core type, which opens around an energized conductor.

Resin-cast CT: extra protection in harsh environments

Environments with conductive dust, moisture or sharp temperature swings wear conventional insulation faster than the design anticipates. Epoxy resin encapsulation adds a layer of mechanical protection and insulation against these factors, the same finishing principle applied in the power transformer line for critical applications.

For whoever specifies equipment that will run in an uncontrolled industrial environment, this is the difference between a part that lasts the project's life cycle and one that needs replacing earlier than planned. The impact shows in the panel's total cost of ownership, not in the initial quote.

Split-core current transformer potted in black epoxy resin, with fixing screws that close the core around the conductor and two output leads
Epoxy resin encapsulation: the same part gains mechanical protection and insulation against moisture and conductive dust.

CTs in SCADA: field data the automation can trust

A SCADA system is only as good as the data that reaches it. A current transformer with an accuracy class unsuited to the measurement point creates an error that propagates through the whole supervision chain, and that nobody notices until the field data stops matching the energy balance.

Specifying the CT for the instrumentation point, and not just for the panel in general, is what gives the supervision system stability from the first day of operation.

Set of three toroidal current transformers mounted on a phenolic board, wired to a numbered terminal block
Set of three CTs mounted on a board, with an identified terminal block, ready to go into the panel.

CTs for automatic reclosers: robustness on the distribution network

An automatic recloser operates on the distribution network, exposed to short circuits, transient overcurrent and successive reclosing cycles in a short interval. The current transformer feeding that equipment's protection has to hold its accuracy and reliability under this duty, which is more demanding than normal operation of an industrial panel.

It is one of the cases in which short-circuit robustness weighs as much as accuracy class in the specification decision.

How we test every CT before shipping

100% of the current transformers we produce go through electrical testing before leaving the factory, not by sampling. The laboratory measures no-load voltage and current, error and saturation behavior, phase angle, inductance, insulation and polarity.

These are the same parameters that define whether a CT will behave as expected in the field: error and saturation confirm the declared accuracy class, and phase angle and polarity prevent installation rework in the panel and in the protection loop.

Before the quote

How to specify a current transformer

This is the information our engineering team asks for to turn a generic quote into a custom specification. The more complete the list, the lower the risk of rework after installation.

  • Application: metering CT, protection CT, or both
  • Rated primary and secondary current, or the turns ratio (the secondary is typically 1 A or 5 A)
  • Rated secondary burden in VA, the load the CT has to drive
  • Accuracy class required by the project or by the utility
  • Maximum equipment voltage and insulation level
  • Rated frequency
  • Expected short-circuit current and thermal factor
  • Minimum inner diameter and maximum outer diameter, set by the conductor or busbar and by the space in the panel
  • Number of cores for metering and for protection
  • Installation environment: indoor, outdoor or harsh industrial
  • Need for a split-core installation, without de-energizing the circuit
  • Finish type

Current transformer line specifications

Accuracy classfrom 0.3%
Secondary current1 A or 5 A
Voltage classup to 1.5 kV
Insulation voltageup to 4 kV
Thermal classA (105 °C); B (130 °C, on request)
Inner diameter5 mm to 350 mm
CT-specific standardABNT NBR6856
Short-circuit withstandper ABNT NBR5356-5

Standard line parameters. Applications outside these ranges are evaluated case by case by engineering.

Questions that come up with this specification

What is the difference between a metering CT and a protection CT?

A metering CT must hold its accuracy under normal operating conditions. A protection CT needs predictable behavior under fault conditions, including short-circuit currents far above rated, so the relay trips at the right time. ABNT NBR6856 classifies the two as distinct categories.

How do you calculate the turns ratio of a CT?

It is the ratio between the rated primary current and the rated secondary current. In a 100/5 A CT the ratio is 20, so the value read on the secondary must be multiplied by 20 to represent the current flowing in the primary.

What is accuracy class in a current transformer?

It is the maximum permissible error between the actual circuit current and the current indicated by the CT, within the specified operating range. The Toroid line starts at 0.3%.

What is saturation in a current transformer?

It is the limit above which the core can no longer follow the primary current and the CT loses its original electrical characteristics. Beyond that point the secondary no longer reproduces the primary faithfully, the declared accuracy no longer holds, and the unit has to be replaced.

What happens if the secondary of a CT is left open?

With no load connected to consume the energy induced in the core, the secondary voltage rises to dangerous levels. This can cause internal arcing, overheating and insulation failure, as well as an electric shock hazard for anyone operating the equipment. The secondary must always be connected to an appropriate rated burden.

Can a split-core CT be installed without de-energizing the circuit?

Yes. A split-core CT opens around the conductor while it is energized, which removes the need to disconnect for installation or maintenance. In exchange, the two cuts in the core reduce accuracy compared with a window-type CT, which has a continuous core.

Which standard governs current transformers in Brazil?

ABNT NBR6856 is the standard specific to current transformers. ABNT NBR5356-5 covers short-circuit withstand capability, which is relevant for protection CTs.

Start from the constraint, not from the product code

If your panel has a space constraint, a specific accuracy requirement, or a history of CTs that did not last as long as expected, describe the constraint to our team before closing the specification. It is faster than comparing catalogs.

Technical quote