Standard-line current transformer
The Isobox arrives panel-ready, with the same tested engineering as the entire Toroid line
The Isobox is the standard line of toroidal current transformers from Toroid do Brasil: 5 A secondary current, 600 V insulation tested at 4 kV and three mounting types already defined, DIN rail, panel back plate or busbar. When the application calls for parameters outside those ranges, the path becomes a custom project, not a catalog adaptation.
- São José dos Pinhais · PR
- Designed to ABNT NBR6856
- Standard line, ready for all 3 mounting types
What the Isobox is
The Isobox is a window-type toroidal current transformer: the circuit conductor passes through the central opening of the core, with no interruption and no need to open the circuit to install it. It steps a high primary current, hard to measure directly, down to a proportional 5 A secondary current that measuring and protection instruments can read safely.
The 600 V insulation, tested at 4 kV, and the thermal class A (105 °C) define how far the Isobox operates with electrical and thermal safety inside the panel. The rated frequency is 60 Hz, the same as the Brazilian grid.

Standard line or custom project
Not every application needs a new specification. When the Isobox secondary current, insulation and mounting type already fit the project, the standard line skips the development step and keeps the same engineering and the same electrical test on 100% of the units leaving the factory.
When the panel requires an inner diameter outside the standard range, a specific accuracy class or a construction different from those available here, the path becomes a custom project, as in the Toroid Current Transformers, Power Transformers and Inductors & Reactors lines.
Available mounting types
The Isobox comes in three mounting types, to cover the most common switchboard arrangements with no bracket adaptation needed in the panel:
- DIN rail. Mounts directly on the standard switchboard rail, with no extra drilling.
- Panel back plate. Fastens directly to the back plate of the enclosure, for projects that do not use a rail.
- Busbar. Follows the geometry of a high-current busbar, with no bracket adaptation.
Before the quote
How to specify an Isobox
This is the information our engineering team asks for to confirm whether the standard line fits your panel, or whether the project needs to be custom.
- Rated primary current of the circuit
- Desired mounting type: DIN rail, panel back plate or busbar
- Diameter of the conductor or busbar that will pass through the central opening
- Rated secondary burden in VA, the load the Isobox needs to drive
- Rated system frequency
- Installation environment: indoor, outdoor or harsh industrial
Isobox standard line specifications
| Secondary current | 5 A |
|---|---|
| Insulation | 600 V (tested at 4 kV) |
| Temperature class | A (105 °C) |
| Rated frequency | 60 Hz |
| Construction type | Window, toroidal core |
| Available mounting | DIN rail, panel back plate or busbar |
Standard line parameters. An application outside these ranges is evaluated by engineering as a custom project.
Questions that come up before the quote
Is the Isobox the same current transformer as the custom line?
It uses the same window-type toroidal core technology and the same electrical test applied across the whole Toroid line. The difference is that the Isobox already comes with secondary current, insulation and mounting defined in the standard line, so it skips the custom specification step.
Which mounting types does the Isobox support?
DIN rail, panel back plate or busbar. The three types cover the most common switchboard arrangements, with no bracket adaptation needed in the panel.
Does the conductor have to be cut to install the Isobox?
No. Because it is a window-type CT, the conductor passes through the central opening of the core without interruption. Installation only requires threading the existing conductor through the transformer window.
When is the Isobox not the right choice?
When the project needs an inner diameter outside the standard range, a specific accuracy class, insulation above 600 V or a different construction type. In those cases, the path is a custom project with Toroid engineering, as in the Current Transformers, Power Transformers and Inductors & Reactors lines.
If the standard line does not fit, the next step is a custom project
Diameter out of range, a specific accuracy class or insulation different from the standard? Describe the application so our team can evaluate a custom project, with the same engineering that tests every Isobox before shipment.
Technical quote
Send the specification, or just the panel's constraint. Our team replies with the sizing.
Voltage, current, available space and applicable standard. If any data point is still missing, our team helps you pin it down.